Resistance figures are for copper at about 75°C and are rounded — aluminum cords and cheap copper-clad wire run 2× or worse, and a cord coiled in a reel adds inductive loss the flat-cable formula here does not count. Any drop over 5% deserves a heavier gauge, a shorter run, or a real circuit installed by an electrician.
The extension cord voltage drop calculator sizes the wire between a grow tent, pump or shop tool and the wall outlet — the piece nearly everyone gets wrong. Longer cords and thinner gauges both waste volts as heat along the cable, so the light or motor at the end sees less than 120 and works harder. Enter gauge, length and amp load, and it returns the drop in volts, as a percentage, and the watts actually cooked off inside the cord. That is the math that decides whether 100 feet of 14 AWG is safe or a slow fire.
The load current goes out on one conductor and returns on the other, so the effective length is twice the cord. Voltage drop = 2 × feet × amps × ohms-per-1000-feet ÷ 1000. A 12 AWG cord runs about 0.64 ohms per thousand feet, which is why 50 feet at 5 amps drops only 0.32 V — but a 14 AWG at 100 feet and 10 amps drops 2 V, and cheap aluminum cords roughly double that again.
Why percentage matters more than volts: a 3-volt drop off a 120 V line is 2.5% and usually invisible, but the same 3 volts off a 24 V low-voltage system is 12.5% and dim. Motors care most, because a low-voltage motor draws extra amps to make the same torque and heats itself; electronics with switch-mode supplies barely notice until the drop is bad enough to make the supply buzz or brown out, and lighting sits in the middle of the sensitivity range.
Approximate copper-conductor resistance in ohms per 1,000 feet at room temperature. Real cords vary with strand count and temperature, and aluminum or copper-clad cords of the same AWG run about 60% higher than the solid-copper figures shown here.
| Gauge | Ohms per 1000 ft | Typical use |
|---|---|---|
| 14 AWG | 1.02 | Short appliance cords, lamps |
| 12 AWG | 0.64 | Hardware-store 25–50 ft |
| 10 AWG | 0.40 | Heavy-duty outdoor, big tools |
| 8 AWG | 0.25 | Welder-grade, long sub-panel runs |
Use it whenever a grow light, pump, tiller or shop tool is run on more than about 25 feet of cord, or fed from a temporary extension for hours at a time. It is US 120 V math; 240 V and 24 V systems behave differently on percentage even though the volt-drop formula is the same. For a permanent wired run to a shed or greenhouse, use a licensed electrician and the appropriate feeders and disconnects rather than a heavier extension cord. And if the load is under 1 A, the drop is almost never a real issue.
Under 25 feet of 12 AWG at normal garden loads, drop is usually negligible. Push the same 12 AWG to 100 feet and any motor over 5 A starts losing real volts. The right answer for anything past 50 feet is a heavier gauge, a shorter route, or a permanent circuit.
Only for a short run under 25 feet at low amperage. Anything longer or heavier and you lose enough voltage that LED drivers buzz, ballasts overheat, and inline fans pull extra current to compensate. Move up to 12 or 10 AWG for the length a real tent usually needs.
Yes, and it wastes it as heat inside the cord itself. The watts consumed along the copper are exactly what does not arrive at the tool, and a long undersized cord can quietly throw off 40–100 W of pure heat — enough to soften cheap insulation over a growing season.
Because motors pull 3–6× their running amps at locked-rotor before they come up to speed, and voltage drop scales linearly with amps. A 100 ft cord that looks fine at 5 A running suddenly drops 3 V at 15 A startup, which is exactly when the pump needs full voltage the most.
Design guides generally cap branch-circuit voltage drop around 3%, with a hard upper bound of 5% total. Sensitive electronics and motors should target 3% or under; incandescent lighting is more tolerant. Anything past 5% is a signal the cord gauge or route needs to change.
The DC resistance stays the same on paper, but a fully-coiled cord traps its own heat and can run dangerously hot under a heavy load — a real fire risk, not a voltage one. Always uncoil an extension cord before pulling anything close to its rated amperage through it.
Chlorova Gardening Team
Builds, checks and documents every tool we publish
Chlorova editorial review
Checked against extension-service publications
How many grow lights, fans and pumps safely fit on a 15 A or 20 A circuit.
Use ToolDaily light integral from PPFD and hours — and the runtime or intensity a crop needs.
Use ToolEmitters, zone flow and weekly run time for drip lines.
Use Tool